Section-9
www.newaveups.com
00-8384_S9_NW_OPMDPA_GB_080808.doc Page 2/8
Printed in Switzerland – Modifications reserved
9.1 OPTIONS
9.1.1 Introduction
The CONCEPTPOWER DPA
TM
is provided with the following accessories:
REMOTE SHUT DOWN FACILITIES
GENERATOR ON FACILITIES
2 CUSTOMER IN FUNTIONS (ON REQUEST)
TEMPERATURE SENSOR FOR TEMP. DEPENDING BATTERY CHARGERING
SOFTWARE FOR AUTOMATIC SHUTDOWN AND MONITORING
SNMP INTERFACES FOR NETWORK MANAGEMENT AND REMOTE MONITORING
MODEM/ETHERNET INTERFACE FOR NEWAVEWATCH
TM
MANAGEMENT SOFTWARE
9.1.2 Remote SHUT DOWN
The REMOTE SHUT DOWN must use a normally closed contact, which opens to operate the remode shut
down sequence.
The remote shutdown on terminal port X1/1.. X1/2 is located at the bottom of the CONCEPTPOWER DPA
TM
frame on communication card with terminal blocks X1 …X4. See section 3 / 1.2.1 for details.
In order to allow removal, maintenance or testing of any remote shut down facility without disturbing the normal
operation of the UPS, it is recommended that a terminal block, with linking facilities, be installed between the
UPS and the stop button.
1. Use a screened cable with 1 pair (section of wires 0.5 mm
2
) and maximum length of 100 m.
2. Connect the cable as shown in Fig. 1.2
REMOTE SHUT DOWN SWITCH
(N.C. = Normally Closed)
UPS
Remote shut down
(X1)
Terminal Block
Fig 1.2 Drawing of the wiring for the REMOTE SHUT DOWN SWITCH.
X 4 X1
X1/1
X1/2